PRE-SHIPMENT DIMENSIONAL, COATING & TRACEABILITY CHECK (PSI)
Product Scope: 1,800 m² Clear-Span Portal Steel Warehouse (S355JR Columns/Rafters, Z200 Purlins & EN 14399 10.9 Bolt Lots — ~74 Tons)
ILLUSTRATIVE CORPORATE SPECIMEN (ZERO CLIENT DATA DISCLOSED): Client names, factory identities, heat/certificate numbers and commercial figures in this specimen are fictionalized to protect strict B2B NDA confidentiality. Scoped commercial/visual engineering record — not an accredited laboratory test certificate or statutory structural sign-off.
01 · ASSIGNMENT REGISTER & EXECUTIVE GATE SUMMARY
Primary portal columns (C-01..C-14) and rafters (R-01..R-14) match shop-drawing overall lengths and splice end-plate hole centers (±1.5 mm). However, 3 rafters showed low epoxy DFT (105–118 µm vs 160 µm spec) along bottom flange edges, and M24×85 Grade 10.9 HV nut/washer boxes lacked EN 14399 k-class batch labels.
02 · SCOPED TECHNICAL OBSERVATIONS, MEASUREMENTS & COMPARISON MATRIX
| Ref. | Subsystem / Inspection Parameter | Buyer Specification / Benchmark | Recorded Field / Desk Evidence | Evidence Basis | Required Buyer / Supplier Gate Action |
|---|---|---|---|---|---|
CHK-01 |
Splice End-Plate Thickness & Bolt-Hole Pitch | 25 mm S355JR end-plate; 26 mm holes @ 120×220 mm gauge (±2.0 mm) | Sampled 8 rafters + 6 columns: plate thickness 25.1–25.3 mm; hole centers within ±1.5 mm; zero flame-cut oval holes. | Observed / Verified | Dimensional geometry accepted for site bolting. |
CHK-02 |
Hard-Stamped Piece Marks vs. Erection Drawing | Hard-stamped + tag-labeled member IDs (C-01..C-24, R-01..R-24) | Hard stamps legible under primer/topcoat on all 14 sampled primary members; barcode tags wired. | Observed / Verified | Compliant; retain tag register in packing list. |
CHK-03 |
ISO 12944 Epoxy/PU Coating Dry-Film Thickness (DFT) | Nominal 160 µm total DFT (80% >=160 µm, min >=128 µm rule) | Web faces averaged 174 µm; 3 rafters (R-04, R-09, R-11) measured 105–118 µm along lower flange edges. | Open / Hold Gate | Hold R-04, R-09, R-11 for stripe-coat rework + re-measurement photo. |
CHK-04 |
EN 1090-1 FPC Certificate & Factory NDT Dossier | Valid Notified Body FPC (EXC2), WPS/WPQR and UT/MT report on full-pen welds | Reviewed Notified Body FPC cert, welder quals and third-party UT report #UT-882 covering haunch butt welds. | Document Reviewed | Include signed DoP + UT report PDF in final customs/handover binder. |
CHK-05 |
Cold-Formed Roof Z-Purlins & Eave Struts | Z200 × 2.00 mm S350GD+Z275 pre-punched sleeves, strapped on timber skids | 4 sampled Z200 bundles measured 2.01–2.03 mm coated; zinc surface dry with zero white-rust staining. | Observed / Verified | Ready for loading; keep indoor storage until trailer arrival. |
CHK-06 |
Anchor Bolts & EN 14399-3/4 Grade 10.9 HV Fasteners | Sealed kegs with matching 10.9 bolt, nut & washer batch certificates + +5% spare | M24 10.9 bolt kegs present, but 4 nut cartons were generic 8.8 stock instead of matched EN 14399 HR/HV 10.9 nuts. | Open / Hold Gate | Mandatory replacement with certified Class 10 HV nuts before truck loading. |
Scoped B2B visual field verification, random dimensional spot-sampling and documentary cross-check.
Field gauges zero-checked prior to measurement; heat/batch IDs cross-referenced against presented 3.1 MTCs.
Advance or balance wire release remains conditional upon closing all Open / Hold items logged on Sheet 2.
SSR-2026-PEB-03 · Page 1 / 2
SSR-2026-PEB-03
Rev. 02 · 2026-11-02
Page 2 / 2
03 · CROSS-REFERENCED EVIDENCE & ANNEX REGISTER
MEAS-A1
Logged in Dossier
Recorded web/flange/length/diagonal and end-plate hole pitch measurements vs. shop drawings.
DFT-B2
Logged in Dossier
bay-by-bay DFT readings identifying R-04, R-09 and R-11 flange edge touch-up zones.
CERT-C3
Logged in Dossier
Cross-checked S355JR plate heat numbers and ultrasonic test report #UT-882.
BOLT-D4
Logged in Dossier
Photographic log catching mismatched Class 8.8 nut cartons prior to dispatch.
04 · OPEN-ITEMS ACTION REGISTER BEFORE COMMERCIAL RELEASE
| Item ID | Open Technical / Commercial Point | Action Owner | Target Release Gate |
|---|---|---|---|
OI-01 |
Apply polyurethane topcoat touch-up on R-04, R-09 and R-11 flange edges to >=160 µm DFT and submit gauge photos. | Fabricator QC | Before Trailer Loading |
OI-02 |
Replace mismatched Class 8.8 nut cartons with EN 14399 Class 10 HV nuts + 3.1 fastener batch certificate. | Fabricator Purchasing | Before Balance Release |
OI-03 |
Confirm timber spacer dunnage between painted rafters during 13.6 m mega-trailer loading (SS-LOAD €390). | Fabricator / SerSourcing | Loading Day |
05 · EVIDENCE CLASSIFICATION KEY & CORPORATE SCOPE GOVERNANCE
Directly witnessed, counted or measured on site/desk by SerSourcing within the agreed assignment window.
Recorded from supplier-submitted certificates, MTCs or drawings without assuming physical lot testing.
Verbal or written manufacturer statement recorded transparently; requires independent verification.
Unresolved technical or commercial hold item recommended for closure prior to stage payment/dispatch.
Governance & Independence Standard: Issued under buyer-representation tariff SS-2026-11-V2. Zero undisclosed supplier commission. Goods contracts, product warranties, accredited EN ISO/IEC 17025 lab testing and statutory engineering sign-off remain with the respective contracting parties and appointed specialists.
06 · DOCUMENT REVISION LOG & CONTROLLED DISTRIBUTION REGISTER
| Rev. | Date | Revision Status & QA Milestone | Authorized Distribution & Archive Retention |
|---|---|---|---|
Rev. 01 |
2026-10-30 | Initial field / desk observation log, dimensional check sheet & annex index. | Internal Engineering Desk QA Review (Maltepe HQ) |
Rev. 02 |
2026-11-02 | QA-verified corporate engineering dossier & executive gate recommendation. | Commissioning Buyer (1× Encrypted PDF + Annex ZIP) · 5-Yr NDA Archive |
07 · BUYER CONTRACT, PAYMENT & DISPATCH SAFEGUARD PROTOCOL
GATE-01
Proforma & Technical Specification Rider
Bind verified steel grade, coating mass, tolerances and export packing rules directly into the signed Proforma Invoice.
GATE-02
Lot-Specific Certificate & Export Pack
Verify batch-allocated EN 10204 3.1 MTC, CE DoP, packing list and draft A.TR/EUR.1 48h prior to balance wire.
GATE-03
Pre-Shipment & Loading Gate Witness
Confirm final piece count and dunnage via SS-PRE (€490) or SS-LOAD (€390) before high-security bolt seal closure.
GATE-04
Strict NDA & Zero-Commission Mandate
Issued exclusively for commissioning buyer internal governance; SerSourcing accepts zero supplier commission (0%).